U.S. manufacturer-source guide. Last checked November 20, 2026. A home battery advertised for 240 V is not automatically suitable for every property with a 120/208 V service. The exact inverter, battery controller, gateway, transfer equipment and electrical service all need to match.
This matters for some condominiums, townhomes and multi-unit buildings, but the building type alone does not identify its electrical service. Do not assume that every apartment or condo has 120/208 V, or that every detached home has 120/240 V. Have a licensed electrician identify the service at the property.
120/208 V and 120/240 V are different service arrangements
Both labels include 120 V circuits, but the line-to-line voltage and electrical arrangement differ. A product specification for 120/240 V split-phase service does not prove that the same product supports a 120/208 V service. The exact voltage, phase, neutral arrangement and installation instructions must be checked for the complete system.
What the manufacturer sources establish
| System / component | Published service information | How to interpret it |
|---|---|---|
| FranklinWH aPower X or aPower 2 + aGate | FranklinWH lists 120/240 V and 120/208 V, 60 Hz in its published component specifications. aPower X is listed at 13.6 kWh; aPower 2 is listed at 15 kWh AC usable system energy. Its commissioning guide shows separate service-voltage selections for the two arrangements. | Documented support for both listed service options, subject to the exact aPower/aGate model, nameplate, approved configuration and current installation documentation. |
| FranklinWH aPower S + compatible aGate | FranklinWH lists nominal AC voltage of 120/208 V and 120/240 V, single phase, in its published aPower S component specifications. The published component information lists 15 kWh usable energy per unit and an integrated inverter. | Documented support for both listed service-voltage options at the product-specification level. Confirm the exact aGate generation, system SKU, commissioning setup and approved design; this does not establish compatibility with every third-party smart panel. |
| Anker SOLIX Home Power Panel | Anker states that the panel supports 120/240 V split-phase systems only and does not support 120/208 V systems. | Documented mismatch for a property confirmed to have 120/208 V service. Do not assume a 120/240 V product rating can be adapted to this service. |
| EcoFlow Smart Home Panel 2 | The owner manual describes Smart Home Panel 2 as a split-phase system and documents 120/240 V operation. The checked sources do not establish 120/208 V support. | Not enough information to claim 120/208 V compatibility. Lack of evidence is not proof that every possible configuration is incompatible. |
| SPAN Panel + a compatible battery | SPAN lists model-specific battery integrations, but its support article says the SPAN Panel requires 120/240 V split-phase AC service. | Documented mismatch for a property confirmed to have 120/208 V service, even when a separately listed battery system supports 120/208 V. Check the SPAN and battery system requirements independently. |
FranklinWH: the documented 120/208 V example
FranklinWH’s current component information lists nominal AC voltage options of 120/240 V and 120/208 V for the aGate, aPower X, aPower 2 and aPower S. The published tables list 13.6 kWh for aPower X and 15 kWh for both aPower 2 and aPower S; these products have different inverter architectures and must not be treated as interchangeable. The commissioning guide also shows distinct service-voltage choices for 120/240 V single-phase, 3-wire and 120/208 V single-phase, 3-wire. This is stronger evidence than inferring compatibility from a generic 240 V headline.
That does not make every FranklinWH generation, battery combination, gateway, existing solar inverter or SPAN integration automatically suitable. Check the exact nameplate and the current system design and commissioning documents. A licensed installer must confirm the approved configuration for the property.
Why Anker and EcoFlow should not be treated the same
Anker explicitly excludes 120/208 V service for its Home Power Panel. This is a documented service-type limitation, not merely missing information.
EcoFlow’s Smart Home Panel 2 documentation describes a split-phase arrangement and specifies 120/240 V operation. The sources checked for this guide do not establish that the SHP2 supports 120/208 V. We therefore label the question “not enough information” rather than inventing a yes or no answer.
For exact station combinations, read our EcoFlow Smart Home Panel 2 compatibility guide, the Anker F3800 Plus transfer-switch guide, and the portable home backup panel compatibility matrix.
A separate check for smart electrical panels
SPAN publishes different battery-compatibility lists for SPAN Panel MAIN 32, MAIN 16, MAIN 40, MLO 24 and MLO 48. Some combinations require specific gateways, communication links or the SPAN Remote Meter Kit. Even when SPAN lists a battery and panel as compatible, verify the battery system’s service voltage and phase separately. See our SPAN Panel battery compatibility matrix.
What to ask your licensed electrician to confirm
- The property’s actual service voltage and phase—not an assumption based on building type or a photo of the panel.
- The exact battery model, inverter, gateway/controller and approved system configuration.
- Whether the manufacturer supports that service arrangement in the current U.S. installation documentation.
- The transfer equipment or smart panel, backed-up load center, grounding/neutral arrangement, circuit capacity and local permitting requirements.
- Whether the existing solar inverter, generator or other energy equipment is included in the manufacturer’s approved design.
Do not remove panel covers, probe electrical equipment, change wiring or attempt a connection based on this article. Fixed battery and electrical-panel work must be specified and installed by qualified, appropriately authorized professionals under the applicable code and manufacturer instructions.
Research limitation: The classifications above refer only to what the cited manufacturer documents say about service voltage or supported integration. They are not a site-specific compatibility verdict, electrical design, load calculation, certification or installation approval. Manufacturer specifications can change; re-check the current documents before purchase.
Official manufacturer sources
- FranklinWH — Components of Franklin Home Power (aPower X, aPower 2 and aPower S specifications)
- FranklinWH — Documentation Center, current product-specific installation guides
- FranklinWH — Commissioning Guide
- FranklinWH — aGate 1.3 / aPower 2 System Installation Guide (June 2026)
- SPAN Support — SPAN Panel service-voltage requirement (120/240 V split phase)
- Anker SOLIX — Smart Home Power Kit and Home Power Panel FAQ
- EcoFlow — Smart Home Panel 2 Owner Manual
- SPAN — Panel battery compatibility overview